Quick answer: ACH = CFM × 60 ÷ room volume in cubic feet. A 100 CFM fan in a 12 × 12 × 8 ft room (1,152 cu ft) gives 5.21 air changes per hour, one every 11.52 minutes. In metric, ACH = m³/h ÷ m³: 120 m³/h in a 40 m³ room is 3 ACH.
How to calculate air changes per hour
- Work out the room volume: length × width × ceiling height. 12 × 12 × 8 ft = 1,152 cu ft (32.62 m³).
- Find the airflow of the fan or system in CFM (or m³/h or L/s).
- Multiply CFM by 60 to get cubic feet per hour: 100 × 60 = 6,000 cu ft per hour.
- Divide by the volume: 6,000 ÷ 1,152 = 5.21 ACH.
- Minutes per air change = 60 ÷ ACH = 11.52 minutes.
To find the airflow needed for a target ACH instead, use the CFM calculator: CFM = volume × ACH ÷ 60. For the room volume alone, use the cubic feet calculator.
Air changes per hour by fan airflow and room size
Room volumes for an 8 ft ceiling; ACH = CFM × 60 ÷ volume.
| Room (8 ft ceiling) | Volume | 50 CFM | 100 CFM | 200 CFM |
|---|---|---|---|---|
| 8 × 10 ft | 640 cu ft | 4.69 | 9.38 | 18.75 |
| 10 × 12 ft | 960 cu ft | 3.13 | 6.25 | 12.50 |
| 12 × 12 ft | 1,152 cu ft | 2.60 | 5.21 | 10.42 |
| 12 × 16 ft | 1,536 cu ft | 1.95 | 3.91 | 7.81 |
| 16 × 20 ft | 2,560 cu ft | 1.17 | 2.34 | 4.69 |
The conversions use exact definitions: 1 foot = 0.3048 m, 1 cubic foot = 0.028316846592 m³, 1 L/s = 3.6 m³/h. The room is treated as a simple box; for sloped or vaulted ceilings, work out the volume first and enter an equivalent height.
This page does not apply a ventilation standard or building code. Air changes per hour is a measure of airflow, not of air quality: how well a room is ventilated also depends on where the air comes in and goes out and how well it mixes. Required rates are set by your local code and by standards such as ASHRAE 62.1 and 62.2.
Frequently asked questions
How do I calculate air changes per hour?
ACH = airflow in CFM × 60 ÷ room volume in cubic feet. A 100 CFM fan in a 12 × 12 ft room with an 8 ft ceiling (1,152 cu ft) gives 100 × 60 ÷ 1,152 = 5.21 air changes per hour.
How do I calculate air changes per hour in metric?
Divide the airflow in cubic meters per hour by the room volume in cubic meters. 120 m³/h in a 4 × 4 × 2.5 m room (40 m³) is 120 ÷ 40 = 3 air changes per hour. From liters per second, multiply by 3.6 first.
What does 1 air change per hour mean?
That a volume of air equal to the whole room is moved through it once an hour. Because fresh air mixes with the room air rather than pushing it out like a piston, one air change does not replace all of the air; it is a measure of airflow, not of how clean the air is.
How many air changes per hour do I need?
It depends on the use of the room and on your local building code and the standards it adopts (in the US, ASHRAE 62.1 and 62.2). This calculator does not apply any of them; use the rate your code or designer specifies.
How do I find the CFM of my fan?
Use the rated airflow on the fan's label or data sheet. Ducting, grilles and filters reduce it, so the real airflow is usually lower than the rating.
Is this the same as an air leakage (blower door) ACH50 figure?
No. ACH50 is the air leakage of a house measured at 50 pascals of pressure in a blower door test. This page gives the air changes a fan or system delivers to a room at its airflow.
Is this air changes per hour calculator free to use online?
Yes. The CalcWall Air Changes per Hour Calculator is completely free and works online in any browser, on a phone, tablet or computer. There is nothing to download and no account to create, and the math runs right in your browser, so results appear as you type.