Furnace Size Calculator

Find what size furnace your house needs with this furnace size calculator. Enter the heat load from a Manual J report, or your floor area and BTU per sq ft, and it works out the input BTU at your AFUE and the smallest furnace that covers it. This free online furnace size calculator works on any phone or computer, with no sign-up or download.

Jump to:FormulaAFUESize chartExamplesFAQ

The heat load per sq ft is your figure: there is no official table of it. The value filled in is an example only. Sizes are an example list: replace them with the input ratings of the models you are quoted.

Your result

Furnace size (input rating)

— BTU/h

Quick answer: furnace size = heat load ÷ AFUE, rounded up to a real model. If a 2,000 sq ft house loses 30 BTU/h per sq ft (an example figure), the load is 60,000 BTU/h. At 80% AFUE that needs 75,000 BTU/h input, so buy an 80,000 BTU/h furnace.

Furnace size calculator at a glance: input BTU equals heat load divided by AFUE. A 60,000 BTU/h load at 80% AFUE needs 75,000 BTU/h input, so the smallest size that covers it is an 80,000 BTU/h furnace giving 64,000 BTU/h of heat.
Heat load ÷ AFUE = input; round up to the next furnace you can buy.

How to use the furnace size calculator

Start with what you know. The calculator has three modes.

  • Floor area and heat load per sq ft. Type the heated floor area and how many BTU per hour the house loses per square foot on a design day. The figure filled in, 30 BTU/h per sq ft, is only an example. Replace it with your own.
  • The heat load. Type the design heating load from a Manual J report or a contractor’s quote, in BTU/h. This is the best input you can give it.
  • Check my current furnace. Type the input rating from the old furnace’s data plate and its AFUE. You get the heat it delivers, per sq ft if you add the floor area, and how far it is above your load if you add that.

Then set the AFUE of the furnace you are looking at, any duct losses that are not already in the load, and the list of sizes you can choose from. The list filled in, 40 to 120 thousand BTU/h in steps of 20, is an example. Type the input ratings from the quotes you have, and the calculator picks the smallest one whose output covers the load.

The result shows the size, its heat output and how far above the load it is. It also shows the next size down and how short that one falls. Share the link to send the same numbers to your installer, or add them to your list.

What size furnace do you need?

A furnace has to replace the heat the house loses on a cold day. That loss is the design heat load, in BTU per hour. Everything else follows from it.

  1. Heat load = heated floor area × heat load per sq ft, or the load from a Manual J report.
  2. Output needed = heat load ÷ (1 − duct losses). With no duct losses to add, it equals the load.
  3. Input needed = output needed ÷ AFUE. At 80% AFUE you divide by 0.8.
  4. Furnace size = the smallest input rating in your list whose output, input × AFUE, is at least the output needed.

Input BTU/h = heat load ÷ (1 − duct loss) ÷ AFUE

From heat load to furnace sizeHeat load60,000BTU/hOutput needed60,000BTU/hInput needed75,000BTU/hFurnace size80,000BTU/h÷ (1 − duct loss)here 0%÷ AFUEhere 80%round up to a size80,000 × 80% = 64,000 outThe heat load comes from a Manual J report, or from floor area × your BTU/h per sq ft.
A 60,000 BTU/h load at 80% AFUE needs 75,000 BTU/h input. The next size up is 80,000.

Why round up and not to the nearest size? A furnace a little under the load leaves the house short of heat on the coldest days. A furnace a little over it just runs a bit less. So the furnace size calculator picks the first size that covers the load and shows the one below it, so you can see how close it was.

For the floor area, measure the rooms you heat. Add every heated floor. Leave out the garage, crawl spaces and attics. A finished basement that you heat counts.

Heated floor area: add every heated floor, leave out the garageGround floor40 × 30 ft = 1,200 sq ftGaragenot heated: 040 ft30 ftUpper floor40 × 20 = 8001,200 + 800= 2,000 sq ftMeasure outside the rooms you heat. Count a finished, heated basement; skip crawl spaces and attics.
Ground floor 1,200 sq ft plus upper floor 800 sq ft: 2,000 sq ft heated. The garage is left out.

If your house is measured in square meters, switch the units. The square meters calculator helps with rooms that are not simple rectangles.

BTU per square foot: there is no official number

Most furnace calculators on the web ask for a climate zone and multiply the area by a fixed BTU per sq ft. The three we read did not say where their figures came from. We looked for a primary source: the Department of Energy, ENERGY STAR and the national labs. We did not find a published table of heating BTU per square foot by climate zone.

So this calculator does not pretend to have one. The heat load per sq ft is your input. That is honest, and it is also more useful. Two houses of the same size in the same town can need very different furnaces. Insulation, windows, air leaks, ceiling height and the number of outside walls all change the load.

Here is what the area method gives for a few house sizes, if your figure is 20, 30, 40 or 50 BTU/h per sq ft. These are not climate figures. They show how much the answer swings with the factor.

Heated areaAt 20 BTU/h per sq ftAt 30At 40At 50
1,000 sq ft20,00030,00040,00050,000
1,500 sq ft30,00045,00060,00075,000
2,000 sq ft40,00060,00080,000100,000
2,500 sq ft50,00075,000100,000125,000
3,000 sq ft60,00090,000120,000150,000

Heat load in BTU/h = area × factor. Plain arithmetic; the factors are examples, not recommendations.

Where can your own figure come from? The best place is a Manual J report: divide its heating load by the heated area. Next best, use the check mode on your current furnace. It shows the most heat that furnace can deliver per sq ft. If the house stays warm on the coldest nights, the real load is that much or less. Old furnaces are often oversized, so treat it as a ceiling, not a target.

Your climate zone matters too. Colder places have bigger loads. The PNNL guide to climate zones by county lists the zone for every US county. Give it to your contractor along with the house details.

Input vs output BTU (AFUE)

A furnace burns fuel at its input rating and delivers heat at its output. The difference goes up the flue. AFUE, annual fuel utilization efficiency, links the two. The Department of Energy defines it as the furnace’s annual heat output divided by the fuel energy it uses in a year. An AFUE of 90% means 90% of the energy in the fuel becomes heat for the home and the other 10% escapes.

AFUE: input BTU in, output BTU to the houseFurnaceAFUE 90%Input (fuel)100,000 BTU/hOutput (heat)90,000 BTU/h10% up the flueOutput = input × AFUE. Duct losses come after this and are not in AFUE (US DOE).
At 90% AFUE, 100,000 BTU/h of fuel gives 90,000 BTU/h of heat.

So a higher AFUE furnace can have a smaller input rating for the same house. The table shows the AFUE ranges the DOE gives, and the input you would need for 60,000 BTU/h of heat.

Furnace type (US DOE)AFUEInput for 60,000 BTU/h output
Older, low-efficiency systems56% to 70%107,143 to 85,714 BTU/h
Mid-efficiency systems80% to 83%75,000 to 72,289 BTU/h
High-efficiency systems90% to 98.5%66,667 to 60,914 BTU/h
All-electric furnaces95% to 100%63,158 to 60,000 BTU/h

AFUE ranges from the DOE “Furnaces and Boilers” page. Input = 60,000 ÷ AFUE.

This is why replacing an old 100,000 BTU/h furnace with a new one of the same input can be a mistake. At 60% AFUE the old one gave 60,000 BTU/h of heat. A new 96% furnace with the same input gives 96,000. If the load did not change, the new one could be far too big.

Furnace size chart by heat load

This chart uses the example list of sizes, 40,000 to 120,000 BTU/h input, and two common AFUE levels. It shows the smallest size whose output covers each load.

Heat loadInput at 80%Size at 80%Input at 96%Size at 96%
40,00050,00060,00041,66760,000
50,00062,50080,00052,08360,000
60,00075,00080,00062,50080,000
70,00087,500100,00072,91780,000
80,000100,000100,00083,333100,000
90,000112,500120,00093,750100,000
100,000125,000over 120,000104,167120,000

All figures in BTU/h, no duct losses. Size = smallest input in the list with input × AFUE ≥ load.

Look at the 60,000 row. At 96% AFUE you need 62,500 BTU/h input, just over a 60,000 furnace. That 60,000 model gives 57,600 BTU/h, 4% short. So you still end up with an 80,000 model. Real model lists have more steps than this one, so type the sizes you are actually quoted.

Output of each size vs a 60,000 BTU/h load40k3238.460k4857.680k6476.8100k8096120k96115.2load 60output at 80% AFUE (thousand BTU/h)output at 96% AFUE
Output of each size at 80% and 96% AFUE. Only sizes above the dashed line cover a 60,000 BTU/h load.

Duct losses

AFUE stops at the furnace. The DOE notes that it does not include heat lost from the ducts or pipes, and that this can be as much as 35% of the furnace’s output when the ducts are in an attic, garage or other partly conditioned or unconditioned space.

A Manual J report may already include duct losses in the load. If it does, leave the duct box at 0. If your load is for the rooms only, enter a percentage. The calculator divides by (1 − loss), so 15% turns a 60,000 BTU/h load into 70,588 BTU/h of output needed.

The DOE also notes that energy-efficiency improvements can save money on a new furnace, because you can buy a smaller unit. The insulation calculator works out the material for attic and wall jobs.

Why a Manual J load calculation is the real answer

The professional way to size a furnace is a load calculation by ACCA Manual J, 8th edition (ANSI/ACCA 2 Manual J – 2016). ACCA describes it as the ANSI-recognized standard for producing HVAC equipment sizing loads for homes.

This furnace size calculator does not do that, and does not try to. It does the arithmetic that comes after a load is known: AFUE, duct losses and real sizes. Use it before you talk to installers, to check a quote, or to compare an 80% furnace with a 96% one.

Ask each installer for the design heating load in BTU/h and how they got it. If one quote is much bigger than the others, ask why. The DOE advises having a heating contractor size the furnace, and says a properly sized one operates most efficiently.

Worked examples

Each example uses the calculator as it stands. The numbers match what the tool shows.

2,000 sq ft house, area method

2,000 sq ft × 30 BTU/h per sq ft (example) = 60,000 BTU/h load. No duct losses. At 80% AFUE: 60,000 ÷ 0.8 = 75,000 BTU/h input. Smallest size that covers it: 80,000 BTU/h, giving 64,000 BTU/h, 6.7% above the load. The 60,000 size gives 48,000, 20% short.

Manual J load, 96% furnace

Load from the report: 48,500 BTU/h. At 96% AFUE: 48,500 ÷ 0.96 = 50,521 BTU/h input. The 40,000 size gives 38,400, 20.8% short. The 60,000 BTU/h size gives 57,600, 18.8% above the load.

Ducts in the attic

Room load 60,000 BTU/h, 15% duct losses not in the load. Output needed 60,000 ÷ 0.85 = 70,588 BTU/h. At 95% AFUE: 74,303 BTU/h input. Size 80,000 BTU/h, giving 76,000, 7.7% above what is needed.

Checking the old furnace

Data plate: 100,000 BTU/h input, 80% AFUE. Output 80,000 BTU/h. Over 2,000 sq ft that is 40 BTU/h per sq ft. A Manual J load of 52,000 BTU/h means the old furnace is 53.8% bigger than the load.

Metric house, 150 m²

150 m² × 80 W/m² = 12 kW load. At 92% AFUE: 13.04 kW input. With the example sizes in kW (11.7, 17.6, 23.4, 29.3, 35.2), the smallest that covers it is 17.6 kW, giving 16.2 kW, 34.9% above the load. The 11.7 kW size gives 10.8 kW, 10.3% short.

The old-furnace check is often the eye-opener. It is common to find the existing unit well above the load, which the DOE also points out. The new furnace does not need to match the old one.

Notes for pros

Size on output. The pick compares input × AFUE with the load, so an 80% and a 96% unit of the same input are not the same size.

Ducts once only. Enter duct losses only when the Manual J load leaves them out, or they are counted twice.

Your model list. Replace the example sizes with the input ratings of the line you install, in thousand BTU/h or kW.

Share the numbers. The link carries load, AFUE, ducts and sizes, so a homeowner can open the same result.

  • This tool does not do a load calculation, select equipment by airflow or check a code. Heating load comes from Manual J; equipment selection and local rules are the contractor’s job.
  • For airflow at the registers, the CFM calculator and the air changes per hour calculator cover the room side.

Sources

Where the numbers on this page come from. Everything else is plain geometry and unit conversion, which the calculator does with exact factors.

  • Furnaces and Boilers, U.S. Department of Energy (energy.gov, Energy Saver), web page, undated (read 13 November 2026). Used for: the AFUE definition (annual heat output ÷ annual fuel energy consumed) and its 90% example; AFUE ranges of 56–70% (older systems), 80–83% (mid-efficiency), 90–98.5% (high-efficiency) and 95–100% (all-electric); AFUE not including duct or piping losses, which can be as much as 35% of the furnace output when ducts are in an attic, garage or other partly conditioned or unconditioned space; efficiency improvements letting you buy a smaller unit; a properly sized furnace operating most efficiently, and many existing systems being oversized
  • Manual J Residential Load Calculation, 8th Edition (ANSI/ACCA 2 Manual J – 2016), Air Conditioning Contractors of America (ACCA), 8th edition, ANSI/ACCA 2 Manual J – 2016 (product page read 13 November 2026). Used for: named as the professional method: ACCA describes it as the ANSI-recognized standard for producing HVAC equipment sizing loads for homes. We did not read the manual itself and use none of its tables
  • Guide to Determining Climate Zone by County: Building America and IECC 2021 Updates (PNNL-33270), Pacific Northwest National Laboratory for the U.S. Department of Energy, October 2022. Used for: where to look up the climate zone of a US county (zones as used in the 2021 IECC). The calculator has no built-in factor per zone
  • Guide for the Use of the International System of Units (SI), NIST Special Publication 811, National Institute of Standards and Technology (A. Thompson, B. N. Taylor), 2008 edition, Appendix B.8. Used for: 1 Btu_IT/h = 0.2930711 W, for kW and W/m² in metric mode
  • NIST Handbook 44, Appendix C: General Tables of Units of Measurement, National Institute of Standards and Technology, 2026 edition. Used for: 1 sq ft = 0.09290304 m² (exact)

Frequently asked questions

What size furnace do I need for a 2,000 sq ft house?

It depends on how much heat the house loses, not only its size. If it loses 30 BTU/h per sq ft on the coldest design day, the load is 60,000 BTU/h, and an 80% AFUE furnace needs 75,000 BTU/h input: an 80,000 BTU/h model. At 20 BTU/h per sq ft a 60,000 BTU/h furnace covers it; at 40 you need 100,000. A Manual J load calculation tells you which figure is yours.

What does 80% vs 96% AFUE mean for furnace size?

AFUE is the share of the fuel energy that becomes heat in the house (US DOE). A 100,000 BTU/h input furnace gives 80,000 BTU/h of heat at 80% AFUE and 96,000 at 96%. So a higher AFUE needs a smaller input rating for the same load. For a 60,000 BTU/h load: 75,000 input at 80%, 62,500 at 96%.

Is a bigger furnace better?

No. The Department of Energy says a properly sized furnace operates most efficiently, and warns that many existing systems are oversized. A bigger furnace also costs more to buy. Pick the smallest size whose output covers your design heat load, and let the contractor confirm it.

How many BTU per square foot do I need for heating?

There is no official number. Charts on the web give ranges by climate, but we found no DOE, ENERGY STAR or national-lab source for them, so the calculator does not use one. Get your figure from a Manual J report (heat load ÷ heated floor area), or enter the load directly. The check mode shows what your current furnace delivers per sq ft.

Is furnace size input or output BTU?

Both appear on furnace data. Input is the fuel burned per hour; output is the heat delivered, input × AFUE. Your heat load must be covered by the output. Check which one a quote names: the calculator shows both, and it picks the size by comparing output with the load.

What is a Manual J load calculation?

ACCA Manual J (8th edition, ANSI/ACCA 2 Manual J – 2016) is the procedure HVAC contractors use to work out a home’s heating and cooling loads. ACCA calls it the ANSI-recognized standard for producing equipment sizing loads. Its result, the design heating load in BTU/h, is the number to type into this calculator.

Does my climate zone change the furnace size?

Yes, a colder climate raises the heat load for the same house, and Manual J accounts for it. The PNNL climate zone guide lists the zone of every US county. The calculator has no zone factor built in because we could not find a primary source for one; it works from the load or the per-sq-ft figure you enter.

Do duct losses change the furnace size?

They can. AFUE does not include heat lost from ducts, which the DOE says can be as much as 35% of the furnace output. If your heat load does not already include duct losses, enter a percentage and the calculator raises the output needed. If the Manual J report already includes them, leave it at 0.

Can I use the furnace size calculator in kW and m²?

Yes. Switch the units to m² and kW, or pick a metric country. The load per area is then in W/m² and the sizes in kW, converted with 1 BTU/h = 0.2930711 W (NIST SP 811). AFUE is a US rating, so check how a boiler or furnace sold in your country states its efficiency.

Is this furnace size calculator free to use online?

Yes. The CalcWall Furnace Size Calculator is completely free and works online in any browser, on a phone, tablet or computer. There is nothing to download and no account to create, and the math runs right in your browser, so results appear as you type.