Quick answer: room CFM = room volume (cu ft) × air changes per hour ÷ 60. A 12 × 12 × 8 ft room at 6 air changes per hour needs 115.2 CFM (195.73 m³/h). Duct CFM = area (sq ft) × air speed (fpm): a 6 in round duct at 700 fpm carries 137.44 CFM.
How to calculate CFM
For a room, from air changes per hour
- Find the room volume: length × width × ceiling height. 12 ft × 12 ft × 8 ft = 1,152 cu ft.
- Choose the air changes per hour (ACH) you need, from your local code, your designer or the equipment maker.
- CFM = volume × ACH ÷ 60: 1,152 × 6 ÷ 60 = 115.2 CFM.
In metric units, airflow in m³/h = volume in m³ × ACH. A 4 × 4 m room with a 2.5 m ceiling is 40 m³; at 6 ACH that is 240 m³/h (66.67 L/s, 141.26 CFM).
To go the other way, from a fan's rated airflow to the air changes it gives a room, use the air changes per hour calculator. For the room volume on its own, use the cubic feet calculator.
For a duct, from size and air speed
- Find the inside cross-section area in square feet. Round: π × d² ÷ 4, with d in feet (6 in = 0.5 ft → 0.1963 sq ft). Rectangular: width × height ÷ 144 for inches (8 × 4 in = 0.2222 sq ft).
- Multiply by the average air speed in feet per minute: 0.1963 × 700 = 137.44 CFM; 0.2222 × 700 = 155.56 CFM.
In metric: a 150 mm round duct (0.01767 m²) at 3 m/s carries 0.0530 m³/s = 190.85 m³/h (53.01 L/s, 112.33 CFM).
CFM through a round duct, by diameter and air speed
From CFM = π × d² ÷ 4 × speed, using the inside diameter. Real ducts lose some area to seams, liners and flex-duct folds, so treat these as the most a clean, straight duct of that size carries at that speed.
| Round duct | at 500 fpm | at 700 fpm | at 900 fpm |
|---|---|---|---|
| 4 in | 43.63 CFM | 61.09 CFM | 78.54 CFM |
| 5 in | 68.18 CFM | 95.45 CFM | 122.72 CFM |
| 6 in | 98.17 CFM | 137.44 CFM | 176.71 CFM |
| 7 in | 133.63 CFM | 187.08 CFM | 240.53 CFM |
| 8 in | 174.53 CFM | 244.35 CFM | 314.16 CFM |
| 10 in | 272.71 CFM | 381.79 CFM | 490.87 CFM |
| 12 in | 392.70 CFM | 549.78 CFM | 706.86 CFM |
Airflow units
| Unit | Equals |
|---|---|
| 1 cubic foot per minute (CFM) | 1.699 m³/h, 0.4719 L/s |
| 1 cubic meter per hour (m³/h) | 0.5886 CFM, 0.2778 L/s |
| 1 liter per second (L/s) | 2.119 CFM, 3.6 m³/h |
| 1 foot per minute (fpm) | 0.00508 m/s (1 m/s = 196.85 fpm) |
The conversions use exact definitions: 1 foot = 0.3048 m, so 1 cubic foot = 0.028316846592 m³. The results assume the air speed you enter is the average across the duct and that the room figure is a simple box (length × width × height); for sloped or vaulted ceilings, work out the volume first and enter an equivalent height. Lighting the same room? The recessed lighting calculator spaces the ceiling lights from the room size and ceiling height.
This page does not apply a ventilation standard, a building code or an HVAC design method. Required ventilation rates, bathroom and kitchen fan sizes and duct sizes are set by your local code and by standards such as ASHRAE 62.1 and 62.2; heating and cooling loads need a full load calculation.
Frequently asked questions
How do I calculate CFM for a room?
Multiply the room volume in cubic feet by the air changes per hour you want, then divide by 60. A 12 × 12 ft room with an 8 ft ceiling is 1,152 cu ft; at 6 air changes per hour that is 1,152 × 6 ÷ 60 = 115.2 CFM.
How do I calculate CFM from duct size?
CFM = duct area in square feet × air speed in feet per minute. A 6 in round duct has an area of π × 0.5² ÷ 4 = 0.1963 sq ft; at 700 fpm it carries 0.1963 × 700 = 137.44 CFM.
How many air changes per hour does a room need?
It depends on the room and on the ventilation rules where you live, which are set by local building codes and standards such as ASHRAE 62.1 and 62.2 in the US. This calculator does not apply any of them: enter the rate your code, designer or equipment maker gives you.
How do I convert CFM to cubic meters per hour?
Multiply by 1.699, because 1 cubic foot is 0.0283168 m³ and an hour has 60 minutes: 100 CFM = 169.90 m³/h = 47.19 L/s.
How do I convert CFM to liters per second?
Multiply by 0.4719. 100 CFM = 47.19 L/s. To go back, multiply L/s by 2.119.
Is this a duct sizing or HVAC load calculation?
No. It converts between room size, air changes, duct size, air speed and airflow. Sizing ducts, fans and heating or cooling equipment needs pressure-loss and load calculations (for example ACCA Manual D and Manual J in the US) done by a qualified person.
Is this cfm calculator free to use online?
Yes. The CalcWall CFM Calculator is completely free and works online in any browser, on a phone, tablet or computer. There is nothing to download and no account to create, and the math runs right in your browser, so results appear as you type.